Analysis of the spatiotemporal temperature fluctuations inside an apple cool store in response to energy use concerns

Tijdschriftbijdrage - Tijdschriftartikel

Energy cost concerns have led to question the temperature and air flow regimes in cool store facilities. In this paper, a CFD model of the air flow and temperature dynamics inside an apple fruit cool store was developed, validated and used to analyze energy cost saving alternatives. Load shifting was attempted by cycling the temperature set point between 1.2 °C and 0.6 °C following a day/night regime. Discontinuous use of the cooling operation, including 12 h on/12 h off; 10 h on/14 h off; and 8 h on/16 h off, was also investigated. The study showed that the air circulation fan is the major source of heat load. Hence, an attempt to reduce energy cost should first deliberate on reducing the fan operation time. The study developed a generic tool to analyze temperature control options inside an apple cool store in response to energy use concerns.
Tijdschrift: International Journal of Refrigeration / Revue Internationale du Froid
ISSN: 0140-7007
Volume: 66
Pagina's: 156 - 168
Jaar van publicatie:2016
BOF-keylabel:ja
IOF-keylabel:ja
BOF-publication weight:1
CSS-citation score:2
Auteurs:International
Authors from:Private, Higher Education
Toegankelijkheid:Open