Multi-step operational modal testing of a multi-span viaduct

Book Contribution - Book Chapter Conference Contribution

© 2018 International Conference on Wireless Communications, Signal Processing and Networking, WiSPNET. All rights reserved. Multi-setup operational modal testing has been performed on a multi-span viaduct in Bruges, Belgium. The viaduct consists of two curved integral bridges with a length of about 800 m in parallel with each other. Each bridge has 23 spans and consists of nearly periodic parts. During the measurement, a number of reference sensors is kept fixed, while the other so-called roving sensors are moved in different setups. Modal identification is first carried out for each setup separately. Next, the identified modal data of different setups are merged. It is observed from the stabilization diagrams that the modes are very closely spaced, resulting in a very high modal density, even under 2 Hz. This results in challenges in the modal identification. First, a high model order needs to be considered, leading to a high computational cost. Second, it is difficult to match the partial mode shapes obtained from different setups, due to the closely spaced natural frequencies. This problem is resolved by comparing both the natural frequencies and the mode shapes at the reference locations in the mode matching.
Book: Proceedings of the 40th IABSE Symposium: Tomorrow’s Megastructures
Pages: S6-37 - S6-44
ISBN:9783857481611
Publication year:2018